Comparison with YS100/YS80

Item
YS1700 YS170 SLPC*E
Front display   Color full-dot LCD Full-dot LCD Meter
Analog display Available (bar and meter displays) Available (bar display) Available (meter display)
Digital display Available Available Not available
Trend display Available Available Not available
Alarm display LCD and LED LCD and LED LED
Dimensions 72 x 144 x 250 mm (DIN) (or YS100 or YS80 housing) 72 x 144 x 320 mm (DIN) or 87 x 182 x 480 mm (YS80 housing) 87 x 182 x 480 mm
Weight 1.6 Kg (Basic type) 2.6 Kg 5.4 Kg
User operations Via front panel Via front panel SV and MV: Via front panel
Parameters: Via side panel
Inputs Analog 5 + 3 5 5
Digital 6 (total of DIs + DOs) + 4 DOs 6 (total of DIs + DOs) 6 (total of DIs + DOs)
Sensor direct 1 (optional: mV, TC, RTD, potentiometer, isolator, twowire transmitter, or pulse; not available for the basic type) 1 (optional: mV, TC, RTD, potentiometer, isolator, twowire transmitter, or pulse) Not available
Outputs Current 1 or 2 1 or 2 1
Voltage 1+1 or 2+1 1 or 2 2
Contacts 6 (total of DIs + DOs) + 4 DOs 6 (total of DIs + DOs) 6 (total of DIs + DOs)
Fail contact 1 1 1
Transmitter power supply

2 (standard),
or 1 isolated (optional) + 1 non-isolated (standard);
24 V DC, 60 mA with overcurrent protector

2 (standard),
or 1 isolated (optional) + 1 non-isolated (standard);
24 V DC, 60 mA
Not available
Control loop Single loop Available Available Available
Cascade Available Available Available
Selector Available Available Available
Dual loop Available Available Not available
PID calculation PID, P, sample PI, and batch PID PID, P, sample PI, and batch PID PID, sample PI, and batch PID
Control period 50, 100, or 200 ms 50, 100, or 200 ms 100 or 200 ms
STC Available Available Available
Programming tool PC (USB connection) PC SPRG programmer
Programming method Text programming or function
block programming
Text programming Text programming
Programming capacity Text programming: 1000 steps (main + sub) Function block programming: 400 modules 400 steps (main and subprograms) Main: 99 steps
Sub: 99 steps
Hard manual device Available Available Not available
DCS communication Direct connection (CS 3000) or via SCIU (CS 1000/CS 3000) Direct connection (CS 3000) or via SCIU (CS 1000/CS 3000) Via SCIU (CS 1000/CS 3000)
RS-485 Modbus, PC-Link, or YS100 YS100 Via SCIU
Ethernet Modbus/TCP Not available Not available